Verdampfer auf LPG
We offer different types of LPG vaporizers to increase vaporization capacity of LPG tank.
A vaporizer is essentially a LPG boiler that does not build pressure. LPG enters the vaporizer as a liquid and exits as a gas. Vaporizers are suitable for multiple installations.
Using a vaporizer will help you
- To obtain a constant and sufficient supply of gas vapor even at low temperatures
- To utilize 100% of LPG in your tank and to increase the capacity of the system without adding more tanks
- To avoid re-condensation of vapor in the supply line and tank "freeze-ups"
- To eliminate heavy ends accumulations in tank
- To prevent distillation of LPG mixture and change of combustion characteristics
We offer dry electric, hot water and gas fired vaporizers of American manufacturer Algas-SDI:
Hot Water Powered Vaporizer Unit
We offer a new compact vaporizer unit in stainless steel cabinet with hot water powered HYDREXX vaporizer (Algas-SDI); vaporization capacity 160 / 320 / 500 kg/hr.
The Hydrexx vaporizer is “indirect fired”, meaning no open flame is involved with the heating process. It is a perfect substitute to direct fired vaporizers and can be mounted in close proximity to the tank.
The unit can be installed in zone 1 or 2. The unit is TÜV certified.
The vaporizer unit includes
- Hydrexx vaporizer
- hot water powered
- made from corrosion resistant materials
- operates on any LPG mixture (100% propane to 100% butane)
- perfect for any climate − rated from -40° C
- Wall mount boiler Viessmann ca. 40 KW
- LPG pump Corken with close-coupled motor 2HP, 1 Ph / 230V/ 50Hz
- 1st and 2nd stages regulation and valves
- Stainless steel cylinder cabinet
Dry electric LPG vaporizers
A) Zimmer vaporizer (14 - 40 kg/hod)
Zimmer vaporizers are suitable for commercial, light industrial and residential applications.- Vaporizer is available in two versions: Z40P (for propane) or Z40L (for LPG with max. 80% of butane content).
- Dry electric design: no water, no corrosion, minimal maintenance.
- Vaporization process is self-regulating: no switches, thermostats or relays.
- Installation options: wall mountable, in cabinet, directly on the tank, multiple units’ installation.
- CE marked and ATEX compliant.
Specifications
Vaporization capacity | 14 - 40 kg/hr |
---|---|
Design pressure | 17,24 bar |
Electrical | 120-240V, 50-60 Hz, Phase 1 |
Power input (max.) | 3,27-4,68 kW (0,1 kWh/kg vaporization) |
Weight / dimensions (LxWxH) | 30 kg / 79 x 26 x 16 cm |
Hazardous area classification | Class I, Div 1, Gr D; EEx d IIA T4, Ex II 2G |
Approvals | CE, ATEX, PED (DNV) |
B) TORREXX Vaporizer (25 - 320 kg/hr)
The TORREXX Electric Vaporizer is a single core, dry electric vaporizer that requires no additional remote mounted controls for operation.- Operates on any LPG mixture from 100% propane to 100% butane.
- 98% thermal efficiency.
- Perfect for any climate - rated to -40 C.
- No start/stop switches
- Ready for operation in less than one minute.
Specifications
Model | TX25 | TX50 | TX100 | TX160 | TX240 | TX320 |
---|---|---|---|---|---|---|
Vaporization capacity | 25 kg/hr | 50 kg/hr | 100 kg/hr | 160 kg/hr | 240 kg/hr | 320 kg/hr |
Design pressure | 17,2 bar | |||||
Electrical classification | Explosion proof Class 1, Division 1, Group D EEx d II B T3 / Ex II 2G, NEMKO 04 ATEX 1026X | |||||
Electrical info | 120 – 240 V, Phase 1 | 208 – 415 V, Phase 1,3 | 208 – 480 V, Phase 1,3 | 208 – 480 V, Phase 3 | 380 – 480 V, Phase 3 | 380 – 480 V, Phase 3 |
50 – 60Hz | ||||||
Dimensions (LxWxH) |
32,5 x 32,5 x 115,5 cm | 32,5 x 32,5 x 115,5 cm | 32,5 x 32,5 x 115,5 cm | 32,5 x 32,5 x 130,5 cm | 32,5 x 32,5 x 143,5 cm | 32,5 x 32,5 x 161 cm |
Approvals | CE, PED, ATEX |
Direct Fired vaporizer (80 – 240 kg/hr)
As its name implies, a Direct Fired vaporizer uses direct flame to vaporize liquid LPG inside a heat exchanger. Requiring no electricity, the Direct Fired vaporizer utilizes LPG itself as its source of energy and provides a constant supply of LPG, regardless of the LPG composition. It is perfect for agricultural and industrial applications (crop drying, construction heating, manufacturing processes etc).- No electricity connection required: DF vaporizers run on LPG (consumption is 1 per 80 of vaporized gas).
- Provides complete independence from external energy sources.
- Simple to install, multiple units installation for higher capacities.
- Vaporization capacity remains the same when running on propane or butane.
Specifications
Model | 40/40H | 80/40H | 120/60H |
---|---|---|---|
Vaporization capacity | 80 kg/hr | 160 kg/hr | 240 kg/hr |
Design pressure | 17,2 bar | ||
Burner heat input | 15 kW | 30 kW | 45 kW |
Shipping weight | 70 kg | 100 kg | 125 kg |
Dimensions (DxHxW) | 53x104x56 cm | 53x104x89 cm | 53x127x89 cm |
Construction standards | ASME Section VIII, Division 1, Pressure Equipment Directive 97/23/EC, Module H. | ||
Approvals | CE, PED (DNV) |